| ITEM |
Standard test Method |
ASTM Spec |
Conductive Tile |
Static dissipative Tile |
ELECTRICAL
/ ELECTROSTATIC PROPERTIES
|
 |
Electrical Resistance
-Surface to Surface
-Surface to Ground |
ESD S 7.1 (100V)
ASTM F-150 (100V)
NFPA 99 (500V)
DIN 51953 (500V) |
2.5
X 104~106 Ω
(SD: 106~109)
|
2.5 X 104~106
|
106~108
|
<2.5
X 104~
|
<2.5 X 104~
|
Electrostatic Propensity
(=Static Generation) |
ESD STM
97.2
|
-
|
Less than
20 volts
|
Less than 20 volts
|
 |
Static Decay |
Federal Test Method 101B Method
4046 at 15% Relative Humidity |
< 0.5
sec
|
0.01
sec
|
0.01 sec
|
OTHER
PROPERTIES |
 |
CEN Classification |
DIN EN 685 |
|
Class
34 + 43
|
 |
Composition of Material |
ASTM F 1700
Certificate of Compliance |
|
Homogeneous
|
 |
Thickness |
ASTM F 386, DIN EN 428 |
as specified ±0.005
in. (0.13mm)
|
.118",
3mm
|
 |
Nominal Sizes |
ASTM F 536, DIN EN 427 |
±0.016
in./lin. Ft (0.4mm/304.8 mm)
|
12" x 12"
|
 |
Squareness |
ASTM F 540 |
maximum 0.010
in. (0.25 mm)
|
<0.010"
|
 |
Residual Indentation |
ASTM F1914
DIN EN 433 |
average less
than 8%,
max. single reading 10%
|
< 7%
|
 |
Flexibility |
ASTM F 137 |
no crack or
break
|
No
crack or break
|
 |
Dimensional Stability |
ASTM Fed. Std. No. 501a
Method 6211, DIN EN 434 |
<0.020"/ft
(0.51 mm/304.8 mm)
|
<0.015"/ft
|
 |
Resistance to Chemicals |
ASTM F 925
DIN EN 423 |
No more than
a slight change in surface dulling, surface attack or staining
|
no
more than a slight change in surface dulling, surface attack,
or staining
|
 |
Resistance to Heat |
ASTM F 1514 |
∆<8
ave., max
|
<∆E=2.0
|
 |
Resistance to Light |
ASTM F 1515 |
∆E<8
ave., max
|
<∆E=6.0
|
 |
Static Load Limit |
Modified ASTM F 970-00 |
-
|
2,500
psi
|
 |
Smoke Density |
ASTM E 662 |
<450
|
<450
|
 |
Flame Spread |
ASTM E 84, NFPA 225 |
<75
|
<75
|
 |
Fire Resistance |
DIN 4102 |
|
B1
|
| Critical Radiant Flux |
ASTM E 648, NFPA 253 |
|
>1.08
W/cm2(class I Interior Floor Finish, NFPA Life
Safety code 101)
|
|
Abrasion Resistance |
ASTM D 1044,
CS-10-F Wheel,
500Gm Weight |
|
Cycle
10,000
|
% Gauge Loss
1.60
|
|
| Resistance to Wear |
DIN EN 660-1 |
|
M
|
 |
Effect of Castor Chair |
DIN EN 425 |
|
No
Damage
|
 |
Color Fastness |
ISO 105 B02 |
|
At
least 6
|
 |
Standard for Health Care Faculties |
NFPA 99 |
|
Confirms
to the requirements of NFPA 99 in effect at the time of installation
|
 |
Fulfils product requirements |
DIN EN 649 |
|
yes
|
 |
Underwriters Laboratories |
UL 779 |
|
Meets
UL Standard
|
WARRANTY
|
| |
Free from defects in Workmanship and materials* |
|
|
Ten
Years
|
 |
Conductivity* |
|
|
Lifetime
|